Raritan Branch Circuit Monitor
Data Center Panelboard and Busway Monitoring
- Meters Floor PDU, RPPs, Panelboards, and Busways.
- One controller supports up to 70 power meters.
- Quick configuration via USB stick preloaded with panel schedule.
- CTs connect to live circuits.
- Auto-correct metering adjusts for CT orientation on wires.
- Real-time configurator.
- USB ports for configuration, Wi-Fi networking, and tablet display.
- Supported by DCIM software that offers auto-discovery as a panel.
- Several enclosure options.
- Same firmware as Raritan rack PDUs.
- Remote display using PDView app.
- Collects data on: A, V, kW, kVA, power factor, and kWh.
- Protocols include TCP/IP, Modbus and SNMP.
- Environmental sensor support
Mit dem intelligenten BCM-System (Branch Circuit Monitoring) von Raritan können Sie das volle Potenzial Ihrer Energieinfrastruktur nutzen und die Kapazitäten Ihres wachsenden und sich verändernden
Rechenzentrums verwalten. Ob Sie nun eine vorhandene Anlage umrüsten oder eine neue Anlage aufbauen möchten, das BCM-System von Raritan hilft Ihnen bei der Reduzierung von Energiekosten, Nachverfolgung
des Stromverbrauchs und Minimierung von Ausfallzeiten. Stellen Sie eine Zählerfunktion in Bereichen bereit, die bisher ohne auskommen mussten.
Dieses einfach bereitzustellende modulare System bietet Echtzeitansichten der elektrischen Leistung und des Stromverbrauchs an Abzweigleitungen und der Hauptleitung in einem elektrischen Service-Eingang oder einem fernen Verteilerfeld. Bei leistungs- und umgebungsbezogenen Auffälligkeiten versendet das BCM-System eine Warnmeldung, wodurch sich Ausfallzeiten vermeiden lassen. Die ermittelten Daten unterstützen Kunden bei der Umsetzung von Energieeffizienz- und Abrechnungsinitiativen. Außerdem lässt sich das BCM-System in Power IQ® DCIM Monitoring-Software sowie andere Building Management System (BMS)- und DCIM-Lösungen integrieren.
Dieses einfach bereitzustellende modulare System bietet Echtzeitansichten der elektrischen Leistung und des Stromverbrauchs an Abzweigleitungen und der Hauptleitung in einem elektrischen Service-Eingang oder einem fernen Verteilerfeld. Bei leistungs- und umgebungsbezogenen Auffälligkeiten versendet das BCM-System eine Warnmeldung, wodurch sich Ausfallzeiten vermeiden lassen. Die ermittelten Daten unterstützen Kunden bei der Umsetzung von Energieeffizienz- und Abrechnungsinitiativen. Außerdem lässt sich das BCM-System in Power IQ® DCIM Monitoring-Software sowie andere Building Management System (BMS)- und DCIM-Lösungen integrieren.
Application | Part Number | Description |
Enclosure for monitoring panelboards — suggested for raised floor environments | BCM2-9610Y-KIT-01 | BCM2-9610Y-KIT-01 BCM2-9610Y (Up to 480V, 16A 3PY Terminal, 96 channel branch circuit meter enclosure with controller) BCM2-250A-CT-4PK (4x 250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-1A-CT (1x 1A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-3M (mains circuit cable for 5x CTs) 2x BCM2-60A-CT-12PK (12x 60A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-BCTcable-3M-1, BCM2-BCTcable-3M-2, BCM2-BCTcable-3M-3, BCM2-BCTcable-3M-4 (branch circuit cables for 12x CTs each) BCM2-FLOOR-MOUNT-KIT |
DIN rail modules for monitoring panelboards | BCM2-DIN-KIT-D01 | PMC-1001 (rack/wall mount power meter controller) PMM-1000 (3Phase, 480V DIN rail power meter module) PMB-1960 (96 port power meter branch) BCM2-250A-CT-3PK (3x250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-3M (mains circuit cable for 5x CTs) 2x BCM2-60A-CT-12PK (12 x 60A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-BCTcable-3M-1, BCM2-BCTcable-3M-2, BCM2-BCTcable-3M-3, BCM2-BCTcable-3M-4 |
DIN rail modules for monitoring Busway Mains | BUS-DIN-KIT-D01 | PMC-1001 (rack/wall mount power meter controller) PMM-1000 (3Phase, 480V DIN rail power meter module) BCM2-250A-CT-3PK (3x 250A current transformer / 0.5% / 333mV / 24” / 610mm lead) BCM2-MCTcable-0.5FT (mains circuit cable for 5x CTs) BCM2-1A-CT (1x 1A current transformer / 0.5% / 333mV / 24” / 610mm lead) |
Voltage Measurement Inputs
- Input Range*
- 90–277V LN, 156–480V LL
Measurement Category
- CAT III, Pollution Level 2
Frequency
- 50/60 Hz
Current Measurement Inputs
- CT Type
- Voltage Output = 333 mV at rated current
CT Rated Current
- 1–1200A
Power Requirements
- Voltage
- 90–240V
Current
- 0.2A
Environmental
- Operating Temperature
- 0°–60°C (32°-140°F)
Operating Humidity
- 5–85%
Operating Elevation
- 0-3000m
Meter Measurement Accuracy
- Active Power & Energy
- 0.5%: IEC 62053 Class .5, EN 50470-3 Class C
Reactive Power & Energy
- 2%
RMS Voltage & Current
- 0.2%
Frequency
- 0.1%
Sample Rate
- 64x 50 or 60 Hz (phase locked)
Measurement Update Rate
- 3 secs: IEC 61000-4-30 Class S
Conformance
- Safety
- UL/EN 61010-1
EMC/EMI
- EN61326-1, FCC Part 15 Class A